User Constant Tables
5-
69
* 1. The setting range depends on the setting of L8-32.
L8-32 = 1: 50°C to 130°C
L8-32 = 0: 50°C to 104°C
* 2. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
* 3. Applicable for G7-Series Inverters with software versions PRG 1038 and later.
* 4. Applicable for G7-Series Inverters with software versions PRG 1039 and later.
* 5. If a current exceeding 110% of the Inverter rated current flows through the unit, the carrier frequency will automatically decrease and electromagnetic
noise will occur.
* 6. The lower limits are 0.4 kHz for V/f control and 1.0 kHz for flux vector control. The upper limit is the same value as that of the factory setting for L8-
39.
* 7. Applicable for G7-Series Inverters with software versions PRG 1043 and later.
L8-22
*7
Neutral point
voltage con-
trol selection
Enable or disable neutral
point voltage control for the
400 V Class.
Usually, there is no need to
change this setting.
0: Disabled
1: Enabled
0 or 1 1 No A A A A A 4C3H
Vcn Ctrl Sel
L8-32
*3
OH1 detec-
tion of
Inverters
cooling fan
0: Disabled (FAN minor
fault detection)
1: Enabled (OH1 major fault
detection)
0 or 1 1 No A A A A A 4E2H 6-74
OH1 Detect
Sel
L8-38
*4
Carrier
frequency
reduction
selection
0: Disabled (No carrier
frequency reduction.)
1: Enabled (Carrier
frequency is reduced
accordingly.)
0 or 1
1
*5
No A A A No No 4EFH
Prtct@L-Spd
L8-39
*4
Reduced
carrier
frequency
Sets the reduced carrier fre-
quency.
0, 4 to
2.0
*6
2.0 kHz
*2
*5
No A A A No No 4F0H
L-Spd
Carrier F
L8-41
*4
Current alarm Allows or restricts an alarm
from being triggered when
the relative output current
rises above 150%.
0: Disabled.
1: Enabled (alarm will be
output).
0 or 1 0 No A A A A A 4F2H
6-183
HC Alarm
Sel
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
TOE-S616-60.1.book 69 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals