Individual Functions
6-
109
Related Constants
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
b5-01
PID control
method selec-
tion
0: Disabled
1: Enabled (Deviation is D-
controlled.)
2: Enabled (Feedback value is D-
controlled.)
3: PID control enabled
(frequency reference + PID
output, D control of deviation)
4: PID control enabled
(frequency reference + PID
output, D control of feedback
value).
0 to 4 0 No A A A A A 1A5H
PID Mode
b5-02
Proportional
gain (P)
Sets P-control proportional gain
as a percentage.
P-control is not performed when
the setting is 0.00.
0.00
to
25.00
1.00 Yes A A A A A 1A6H
PID Gain
b5-03
Integral (I) time Sets I-control integral time in 1-
second units.
I-control is not performed when
the setting is 0.0.
0.0 to
360.0
1.0 s Yes A A A A A 1A7H
PID I Time
b5-04
Integral (I) limit Sets the I-control limit as a per-
centage of the maximum output
frequency.
0.0 to
100.0
100.0
%
Yes A A A A A 1A8H
PID I Limit
b5-05
Derivative (D)
time
Sets D-control derivative time in
1-second units.
D-control is not performed when
the setting is 0.00.
0.00 to
10.00
0.00 s Yes A A A A A 1A9H
PID D Time
b5-06
PID upper limit Sets the upper limit after PID-
control as a percentage of the
maximum output frequency.
0.0 to
100.0
100.0
%
YesAAAAA1AAH
PID Limit
b5-07
PID offset
adjustment
Sets the offset after PID-control
as a percentage of the maximum
output frequency.
-100.0
to
+100.0
0.0% Yes A A A A A 1ABH
PID Offset
b5-08
PID first order
lag time con-
stant
Sets the time constant for low
pass filter for PID-control outputs
in 1-second units.
Not usually necessary to set.
0.00 to
10.00
0.00 s Yes A A A A A 1ACH
PID Delay
Time
b5-09
PID output
characteristics
selection
Select forward/reverse for PID
output.
0: PID output is forward.
1: PID output is reverse
(highlights the output code)
0 or 1 0 No A A A A A 1ADH
Output Level
Sel
b5-10
PID output gain
Sets output gain.
0.0 to
25.0
1.0NoAAAAA1AEH
Output Gain
b5-11
PID reverse
output selection
0: 0 limit when PID output is
negative.
1: Reverses when PID output is
negative.
0 limit when reverse prohibit is
selected using b1-04.
0 or 1 0 No A A A A A 1AFH
Output Rev Sel
TOE-S616-60.1.book 109 ページ 017年8月4日 金曜日 午後3時41分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals