Individual Functions
6-
109
Related Constants
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
b5-01
PID control
method selec-
tion
0: Disabled
1: Enabled (Deviation is D-
controlled.)
2: Enabled (Feedback value is D-
controlled.)
3: PID control enabled
(frequency reference + PID
output, D control of deviation)
4: PID control enabled
(frequency reference + PID
output, D control of feedback
value).
0 to 4 0 No A A A A A 1A5H
PID Mode
b5-02
Proportional
gain (P)
Sets P-control proportional gain
as a percentage.
P-control is not performed when
the setting is 0.00.
0.00
to
25.00
1.00 Yes A A A A A 1A6H
PID Gain
b5-03
Integral (I) time Sets I-control integral time in 1-
second units.
I-control is not performed when
the setting is 0.0.
0.0 to
360.0
1.0 s Yes A A A A A 1A7H
PID I Time
b5-04
Integral (I) limit Sets the I-control limit as a per-
centage of the maximum output
frequency.
0.0 to
100.0
100.0
%
Yes A A A A A 1A8H
PID I Limit
b5-05
Derivative (D)
time
Sets D-control derivative time in
1-second units.
D-control is not performed when
the setting is 0.00.
0.00 to
10.00
0.00 s Yes A A A A A 1A9H
PID D Time
b5-06
PID upper limit Sets the upper limit after PID-
control as a percentage of the
maximum output frequency.
0.0 to
100.0
100.0
%
YesAAAAA1AAH
PID Limit
b5-07
PID offset
adjustment
Sets the offset after PID-control
as a percentage of the maximum
output frequency.
-100.0
to
+100.0
0.0% Yes A A A A A 1ABH
PID Offset
b5-08
PID first order
lag time con-
stant
Sets the time constant for low
pass filter for PID-control outputs
in 1-second units.
Not usually necessary to set.
0.00 to
10.00
0.00 s Yes A A A A A 1ACH
PID Delay
Time
b5-09
PID output
characteristics
selection
Select forward/reverse for PID
output.
0: PID output is forward.
1: PID output is reverse
(highlights the output code)
0 or 1 0 No A A A A A 1ADH
Output Level
Sel
b5-10
PID output gain
Sets output gain.
0.0 to
25.0
1.0NoAAAAA1AEH
Output Gain
b5-11
PID reverse
output selection
0: 0 limit when PID output is
negative.
1: Reverses when PID output is
negative.
0 limit when reverse prohibit is
selected using b1-04.
0 or 1 0 No A A A A A 1AFH
Output Rev Sel
TOE-S616-60.1.book 109 ページ 2017年8月4日 金曜日 午後3時41分