6
-110
Monitor Functions
b5-12
Selection of
PID feedback
command loss
detection
0: No detection of loss of PID
feedback.
1: Detection of loss of PID
feedback.
Operation continues during
detection, with the
malfunctioning contact not
operating.
2: Detection of loss of PID
feedback.
Coasts to stop during
detection, and fault contact
operates.
0 to 2 0 No A A A A A 1B0H
Fb los Det Sel
b5-13
PID feedback
command loss
detection level
Sets the PID feedback loss detec-
tion level as a percent units, with
the maximum output frequency at
100%.
0 to
100
0% No A A A A A 1B1H
Fb los Det Lvl
b5-14
PID feedback
command loss
detection time
Sets the PID feedback loss detec-
tion level in s units.
0.0 to
25.5
1.0 s No A A A A A 1B2H
Fb los Det Time
b5-15
PID sleep func-
tion operation
level
Set the PID sleep function start
level as a frequency.
0.0 to
400.0
0.0 Hz No A A A A A 1B3H
PID Sleep
Level
b5-16
PID sleep oper-
ation delay time
Set the delay time until the PID
sleep function starts in seconds.
0.0 to
25.5
0.0 s No A A A A A 1B4H
PID Sleep Time
b5-17
Accel/decel
time for PID
reference
Set the accel/decel time for PID
reference in seconds.
0.0 to
25.5
0.0 s No A A A A A 1B5H
PID SFS Time
H6-01
Pulse train
input function
selection
0: Frequency reference
1: PID feedback value
2: PID target value
0 to 2 0 No A A A A A 42CH
Pulse Input Sel
Con-
stant
Number
Name
Description
Output Signal Level
During Multi-Func-
tion Analog Output
Min.
Unit
Control Methods
MEMO
BUS
Reg-
ister
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
U1-24
PID feed-
back value
Monitors the feedback value
when PID control is used.
The input for the max. fre-
quency corresponds to
100%.
10 V: Max. frequency
(-10 to 10 V possible)
0.01
%
A A A A A 57H
PID
Feedback
U1-36
PID input
volume
PID feedback volume
Given as maximum fre-
quency/100%
10 V: Max. frequency
(-10 to 10 V possible)
0.01
%
A A A A A 58H
PID Input
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
TOE-S616-60.1.book 110 ページ 017年8月4日 金曜日 午後3時41分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals