2
-32
* 1. For a 3-wire sequence, the default settings are a 3-wire sequence for S5, multi-step speed setting 1 for S6 and multi-step speed setting 2 for S7, and jog
frequency reference for S8.
* 2. When driving a reactive load, such as a relay coil, always insert a flywheel diode as shown in Fig 2.17.
* 3. Pulse input specifications are given in the following table.
* 4. Use the photocoupler outputs when the minimum permissible load is 5 VDC or less and 10 mA or less.
Photo-
coupler
outputs
P1 Multi-function PHC output 1
Factory setting: Zero-speed
Zero-speed level (b2-01) or below when ON.
2 to 50 mA at 48 VDC
*2
P2 Multi-function PHC output 2
Factory setting: Frequency agreement detec-
tion
Frequency within 2 Hz of set frequency
when ON.
PC
Photocoupler output common
for P1 and P2
P3
Multi-function PHC output 3
Factory setting: Ready for operation when
ON.
C3
P4
Multi-function PHC output 4 Factory setting: Minor fault.
C4
Relay
outputs
MA
Fault output signal (NO con-
tact)
Fault when CLOSED across MA and MC
Fault when OPEN across MB and MC
Dry contacts
Contact capacity:
10 mA min. 1 A max. at
250 VAC
10 mA min. 1 A max. at
30 VDC
Minimum permissible
load: 5 VDC, 10 mA
*4
MB
Fault output signal (NC con-
tact)
MC
Relay contact output com-
mon
M1
Multi-function contact output
(NO contact)
Factory setting: Operating
Operating when ON across M1 and M2.
M2
Analog
moni-
tor out-
puts
FM
Multi-function analog moni-
tor 1
Factory setting: Output frequency
0 to 10 V/100% frequency
-10 to +10 VDC ±5%
2 mA max.AM
Multi-function analog moni-
tor 2
Factory setting: Current monitor
5 V/Inverter's rated current
AC Analog common
Pulse
I/O
RP
Multi-function pulse input
*3
Factory setting: Frequency reference input
(H6-01 = 0)
0 to 32 kHz (3 kΩ)
MP Multi-function pulse monitor
Factory setting: Output frequency
(H6-06 = 2)
0 to 32 kHz (2.2 kΩ)
RS-
485/
422
R+
MEMOBUS communica-
tions input
For 2-wire RS-485, short R+ and S+ as well
as R- and S-.
Differential input, photo-
coupler isolation
R-
S+
MEMOBUS communica-
tions output
Differential output, pho-
tocoupler isolation
S-
IG Communications shield wire
Low level voltage 0.0 to 0.8 V
High level voltage 3.5 to 13.2 V
H duty 30% to 70%
Pulse frequency 0 to 32 kHz
Table 2.11 Control Circuit Terminals (Continued)
Type
No. Signal Name Function Signal Level
TOE-S616-60.1.book 32 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals