6. Operating with DeviceNet Communications
105
• Object Contents
10 Set_Attribute_
Single
Changes the contents of the speci-
fied attribute.
05 Reset Resets the Inverter.
In-
stance
At-
tribute
Name Contents Setting
Range
Factory Set-
ting (Hex)
Read Write Size
00 01 Object
Soft-
ware
Revision
Indicates the Con-
trol Supervisor ob-
ject's software
revision.
--- 0001 OK --- Word
01 03 Run1 Runs the Inverter
forward.
00: Stop.
01: Run forward.
00,01 00 OK OK Byte
04 Run Rev Runs the Inverter
in reverse.
00: Stop.
01: Run in re-
verse.
00,01 00 OK OK Byte
05 NetCtrl Sets the RUN
command right.
00: Use the RUN
command input
method set in con-
stant n003 (RUN
Command Selec-
tion).
01: Enables the
RUN command
from DeviceNet
(byte 0, bits 0 and
1).
00,01 00 OK OK Byte
06 State Indicates the
Inverter’s status.
02: Inverter prepa-
ration not complet-
ed.
03: Inverter prepa-
ration completed
(stopped).
04: Operating
(normal).
05: Decelerated to
a stop (normal).
06: Decelerated to
a stop because of
serious fault.
07: Stopped be-
cause of serious
fault.
--- 03 OK --- Byte
Service
Code
(Hex)
Service Name Description