106
01 07 Running
1
Indicates the
Inverter’s operat-
ing status.
00: Stopped, oper-
ating in reverse, or
applying DC injec-
tion braking (Re-
verse RUN
command ON).
01: Operating for-
ward or applying
DC injection brak-
ing (Reverse RUN
command OFF).
--- 00 OK --- Byte
08 Running
2
Indicates the
Inverter’s operat-
ing status.
00: Stopped, oper-
ating forward, or
applying DC injec-
tion braking (Re-
verse RUN
command OFF).
01: Operating in
reverse or apply-
ing DC injection
braking (Reverse
RUN command
ON).
--- 00 OK --- Byte
09 Ready Indicates the
Inverters prepara-
tion status.
00: Fault detected
or initializing.
01: Preparations
for operation com-
pleted.
--- 00 OK --- Byte
0A Faulted Indicates that the
Inverter detected
a fault.
00: Normal
01: Fault detected.
--- 00 OK --- Byte
0B Warning Indicates that the
Inverter detected
a warning.
00: Normal
01: Warning de-
tected.
--- 00 OK --- Byte
0C Fault
Reset
Resets the
Inverter from fault
status.
00: ---
01: Reset fault.
00,01 00 OK OK Byte
0D Fault
Code
The fault code in-
dicates which fault
was detected by
the Inverter. (See
note 3.)
--- 0000 OK --- Word
In-
stance
At-
tribute
Name Contents Setting
Range
Factory Set-
ting (Hex)
Read Write Size