EasyManua.ls Logo

YASKAWA Varispeed V7 - Page 159

YASKAWA Varispeed V7
256 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
158
14 SEARCH command from
maximum frequency
SPEED SEARCH command
signal
149
15 SEARCH command from set
frequency
149
16 ACCELERATION/
DECELERATION HOLD
command
150
17 LOCAL/REMOTE selection 136
18 Communications/control cir-
cuit terminal selection
162
19 Emergency stop fault,
NO contact input
Inverter stops for an emer-
gency stop signal input ac-
cording to the Stopping
Method Selection (n005).
When frequency coasting to
a stop (n005 is set to 1) is se-
lected, the Inverter coasts to
a stop according to
Deceleration Time Setting 2
(n022).
Digital Operator displays
. (Lit for fault, flashing
for alarm.)
-
20 Emergency stop alarm,
NO contact input
-
21 Emergency stop fault,
NC contact input
-
22 Emergency stop alarm,
NC contact input
-
23 PID control cancel 184
24 PID integral reset 184
25 PID integral hold 184
26 Inverter overheat alert (OH3
alarm)
-
27 Acceleration/deceleration
time selection 2
-
28 Data input from communica-
tions
92
34 UP/DOWN commands Setting enabled only for
n053 (terminal S4)
160
Setting Name Description Ref.

Table of Contents

Related product manuals