62
• Output (Inverter → Master) Instance 71 (47 Hex)
Data Name Contents
Byte 0,
bit 0
Run Fwd Runs the Inverter forward.
0: Stop.
1: Run forward.
Byte 0,
bit 1
Run Rev Runs the Inverter in reverse.
0: Stop.
1: Run in reverse.
Byte 0,
bit 2
Fault Reset Resets the Inverter from fault status.
0: ---
1: Reset fault.
Byte 0,
bit 5
NetCtrl Sets the RUN command right.
0: Use the RUN Command Input Method
set in constant n003 (RUN Command
Selection).
1: Enables the RUN command from
DeviceNet (byte 0, bits 0 and 1).
Byte 0,
bit 6
NetRef Sets the Frequency Reference right.
0: Use the Frequency Reference Input
Method set in constant n004 (Fre-
quency Reference Selection).
1: Enables the Frequency Reference
from DeviceNet (bytes 2 and 3).
Bytes
2 and 3
Speed
Reference
Sets the Inverter’s speed reference.
The speed reference is exactly the same
as it is in a Basic I/O Instances.
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 At Ref-
erence
Ref
From
Net
Ctrl
From
Net
Ready Run-
ning 2
(Rev)
Run-
ning 1
(Fwd)
Warn-
ing
Fault-
ed
1 --- --- --- --- --- --- --- ---
2 Speed Actual (Low Byte)