6. Operating with DeviceNet Communications
63
3 Speed Actual (High Byte)
Data Name Contents
Byte 0,
bit 0
Faulted Indicates that the Inverter detected a
fault.
0: Normal
1: Fault detected.
Byte 0,
bit 1
Warning Indicates that the Inverter detected a
warning.
0: Normal
1: Warning detected.
Byte 0,
bit 2
Running 1
(Fwd)
Indicates the Inverter’s operating status.
0: Stopped, operating in reverse, or
applying DC injection braking
(Reverse RUN command ON).
1: Operating forward or applying DC
injection braking (Reverse RUN com-
mand OFF).
Byte 0,
bit 3
Running 2
(Rev)
Indicates the Inverter’s operating status.
0: Stopped, operating forward, or apply-
ing DC injection braking (Reverse
RUN command OFF).
1: Operating in reverse or applying DC
injection braking (Reverse RUN com-
mand ON).
Byte 0,
bit 4
Ready Indicates the Inverter’s preparation sta-
tus.
0: Fault detected or initializing.
1: Preparations for operation completed.
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0