6. Operating with DeviceNet Communications
83
• Output (Inverter Master) Instance 155 (9B Hex)
Fnc. Code 1 = 1 Fnc. Code 2 = 0 The data specified in
bytes 6 and 7 will be writ-
ten to the register speci-
fied in bytes 4 and 5.
Fnc. Code 1 = 1 Fnc. Code 2 = 1 Nothing will be executed.
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Fault-
ed
Warn-
ing
Ready At Ref-
erence
Reset Rev
Run-
ning
ZSP Run-
ning
1Termi-
nal P2
Te rm i-
nal P1
Term i-
nal
MA*
Local/
Re-
mote
Fnc.
Code 2
Fnc.
Code 1
UV OPE
2 Speed Actual (Low Byte)
3 Speed Actual (High Byte)
4 Register Number (Low Byte)
5 Register Number (High Byte)
6 Register Data (Low Byte)
7 Register Data (High Byte)
Data Name Contents
Byte 0,
bit 0
Running Indicates the Inverter’s operating status.
0: Stopped.
1: Operating forward, operating in
reverse, or applying DC injection
braking.
Status of Func-
tion Code 1
(Byte 1, bit 1)
Status of Func-
tion Code 2
(Byte 1, bit 2)
Function

Table of Contents