3. Cabling
3-44
TI 33J01J10-01EN
n Connecting Signal Cables to Terminals (for FIO)
l Connecting to Pressure-clamp Terminal
1. Loosen the cable connecting terminal screw.
 
the cable into the connecting section of the pressure clamp terminal.
 
standard with a tip width of 0.6 mm and a shaft diameter of 3.5 mm) with a fastening torque
of 0.5 N•m.
Terminal screwCable terminal
ATA4S-00 S1
F030502.ai
Figure Connecting Signal Cable to Terminal (for FIO)