2. Transportation, Storage and Installation
2-26
TI 33J01J10-01EN
l Mounting of Base plate
 
 

F020514.ai
M4 screw with retainar
Node interface unit base plate
Figure Example of Mounting Node Interface Unit to Wall
Table Tighening Torque for Wall Mountable Devices
Model Torque (N·m)
A2NN30D 0.8~1.0
A2BN3D 0.8~1.0
A2BN4D 1.2
A2BN5D 1.2
l Remarks for Mounting terminal board on a Wall Surface

Installation screws for the terminal board are not supplied and should be purchased separately.
You need two installation screws. If you are using binding heads, use M4 screws with a length of
at least 10 mm. If you are using screws with washers, use M4 screws with a length of at least 12
mm. The screw tightening torque is approximately 0.8 N·m.
Unit: mm
100
±0.5
2-M4 screw holes
110
(40.5)
(93.5)
Device Mounting Area
5
F020529.ai
Figure Screw Installation Dimensions for A2BM4