1. System Installation Requirements
1-27
TI 33J01J10-01EN
n Intersecting Cables


Signal cables
Steel plate (1.6 mm or thicker, grounded)
Unshielded power cables
Protective grounding system
F010603.ai
Figure Intersecting Cables under Pit/Free-access Floor
n Ambient Temperature
The ambient temperature where signal and bus cables are laid must be within the range
-10 to 60 °C.


range -20 to 70 °C.

ambient temperature where the cables are laid must be within the range -40 to 70 °C.

are laid must be within the range -20 to 60 °C.

board (A2BM4), the ambient temperature where the cables are laid must be within the range -20
to 70 °C.
n Measures against EMI



Oct. 5, 2018-00