1. System Installation Requirements
1-3
TI 33J01J10-01EN
n Clearance From The Wall and The Floor Surface




Current flow Wall
1000
mm
or
more
2400 mm
or more
Ceiling
Floor surface
F010101.ai
Ventilation
holes
Side of
Cabinet
Filters (outside)
and fans (inside)
Cabinet Cabinet
Figure Wall Clearance and Ceiling Height
n Illumination



TIP

 
 
 
 
 
(Source: JIS Z9110)
n Outlets for Maintenance

equipment for maintenance.
n Telephone
Telephones should be installed for communications with related stations.