3. Cabling
3-81
TI 33J01J10-01EN
3.7.3 Adaptors (for A2BN3D)
n A2SAP105 Pulse Input Signal Adaptor





used for the following circuit diagrams but the terminal-D cannot be used.
lWhen receiving dry contact signals (Input frequency: 0 to 800 Hz)


F030706.ai
A2SAP105
SW1
4 kohm
SW2
Input filter
12 V DC/24 V DC
INA
INB
INC
IND
Transmiter
: 1 to 16
Figure When receiving dry contact signals (Input frequency: 0 to 800 Hz)
lWhen receiving dry contact signals (Input frequency: 0 to 5 kHz)


F030707.ai
A2SAP105
SW1
4 kohm
SW2
Input Filter
12 V DC/24 V DC
Transmitter
INA
INB
INC
IND
: 1 to 16
Figure When receiving dry contact signals (Input frequency: 0 to 5 kHz)