2. Transportation, Storage and Installation
2-38
TI 33J01J10-01EN
Mar. 29, 2019-00
l Example of Mounting an FCU for N-IO and N-IO Nodes in a Cabinet
Temperature conditions
In this example, the ambient temperature is assumed to be the following.
Cabinet ambient temperature 40 °C or less
Maximum numbers of units that can be mounted in case of this example
Type Model Number of units that can be mounted per side
  Up to 1
NIU A2NN30D Up to 1
IOBP A2BN3D 

Exception to mounting heat-generating devices
Shunt Resistor Unit : A2EXR001 for the Pulse Input Signal Adaptor (A2SAP105) can be mounted
in the same cabinet under the following conditions:
A2EXR001 shall be mounted on the side of the cabinet or under IOBP with a distance of
200 mm from NIU.
 
cabinet shall be reduced in accordance with the following table.
Table Example of Number of A2EXR001 Mounted and Mounting Conditions
Number of A2EXR001 mounted Mounting condition
1 to 4 Can be mounted in the same cabinet
5 to 12 Can be mounted in the same cabinet by reducing one IOBPs
13 to 20 Can be mounted in the same cabinet by reducing two IOBPs
 
A2EXR001 units are mounted on a cabinet.
Mounting conditions
 
ceiling.
 
 

Suitable length of signal cables and power cables should be used.