3. Cabling
3-67
TI 33J01J10-01EN
lWhen Receiving No-Voltage Contact Signals (2)

contacts.

Transmitter
AAP135
(1 k ohm)
RL
SW2
FIL
12 V DC
INA
INB
INC
(SW1: ON, SW2: ON for relay contact
if necessary)
Setting Items by the system generation builder
SW1 (RL) : 1 k ohm
SW2 (FIL) : ON when necessary (*1)
SW1
F030606.ai
 
Figure No-Voltage contact Input (2)
lWhen Receiving Voltage Pulse Signals
SW1
RL
SW2
FIL
12 V DC/24 V DC
INA
INB
INC
Transmitter
(SW1: OFF, SW2: OFF)
Setting Items the system generation builder
SW1 (RL) : OFF (No terminating resistor)
SW2 (FIL) : OFF
+
-
F030607.ai
AAP135
Figure Voltage Pulse Input
Oct. 5, 2018-00