3. Cabling
3-68
TI 33J01J10-01EN
lWhen Receiving Current Pulse By Using the Internal Power to Drive the
Transmitter (2-wire power supply type)
Transmitter
SW1
RL
SW2
FIL
12 V DC/24 V DC
INA
INB
INC
(SW1: ON, RL selection, RL=200 ohm, 500 ohm, SW2: OFF)
Setting Items the system generation builder
SW1 (RL) : Select the value of
RL resistance
SW2 (FIL) : OFF
AAP135
Figure 2-Wire Power Supply Type
current pulse signals. By using the input load resistance (select from None, 200 ohm, 500 ohm),
lWhen Receiving Voltage Pulse By Using the Internal Power to Drive the
Transmitter (3-wire power supply type)
SW1
RL
SW2
FIL
12 V DC/24 V DC
INA
INB
INC
Transmitter
(SW1: OFF, SW2: OFF)
Setting Items the system generation builder
SW1 (RL) : OFF (No terminating resistor)
SW2 (FIL) : OFF
AAP135
Figure 3-Wire Power Supply Type
Oct. 5, 2018-00