C3-5
IM 34M06H62-02E 2nd Edition : June 2008-00
Table C3.3 Input Type Selection (1/2) (SW1-1 = OFF)
Input Type Instrument Range
Input Type
Selector Switch
*2
Software
Setting
Input Range
*1
Default Allowable
Range
SW5 SW1-4 SW1-3 IN
*3
RL RH DEC.P RL RH
Software setting
*
4
0 OFF X
Thermocouple
K
-200.0 to 1370.0C 1
OFF
OFF 1 ($01) -2000 13700 1 -2700 13700
ON 33 ($21) -200 1370 0 -270 1370
-200.0 to 1000.0C 2
OFF 2 ($02) -2000 10000 1 -2700 13700
ON 34 ($22) -200 1000 0 -270 1370
-200.0 to 500.0C 3
OFF 3 ($03) -2000 5000 1 -2000 5000
ON 35 ($23) -200 500 0 -200 500
J
-200.0 to 1200.0C 4
OFF 4 ($04) -2000 12000 1 -2000 12000
ON 36 ($24) -200 1200 0 -200 1200
-200.0 to 500.0C 5
OFF 5 ($05) -2000 5000 1 -2000 5000
ON 37 ($25) -200 500 0 -200 500
T
-270.0 to 400.0C 6
OFF 6 ($06) -2700 4000 1 -2700 4000
ON 38 ($26) -270 400 0 -270 400
B
0.0 to 1600.0C 7
OFF 7 ($07) 0 16000 1 0 18000
ON 39 ($27) 0 1600 0 0 1800
S
0.0 to 1600.0C 8
OFF 8 ($08) 0 16000 1 0 17000
ON 40 ($28) 0 1600 0 0 1700
R
0.0 to 1600.0C 9
OFF 9 ($09) 0 16000 1 0 17000
ON 41 ($29) 0 1600 0 0 1700
N
-200.0 to 1300.0C A
OFF 10 ($0A) -2000 13000 1 -2000 13000
ON 42 ($2A) -200 1300 0 -200 1300
E
-270.0 to 1000.0 C B
OFF 11 ($0B) -2700 10000 1 -2700 10000
ON 43 ($2B) -270 1000 0 -270 1000
L
-200.0 to 900.0C C
OFF 12 ($0C) -2000 9000 1 -2000 9000
ON 44 ($2C) -200 900 0 -200 900
U
-200.0 to 400.0C D
OFF 13 ($0D) -2000 4000 1 -2000 4000
ON 45 ($2D) -200 400 0 -200 400
W
0.0 to 1600.0C E
OFF 14 ($0E) 0 16000 1 0 23000
ON 46 ($2E) 0 1600 0 0 2300
Platinel 2
0.0 to 1390.0C F
OFF 15 ($0F) 0 13900 1 0 13900
ON 47 ($2F) 0 1390 0 0 1390
RTD
JPt100
-200.0 to 500.0C 0
ON
OFF 16 ($10) -2000 5000 1 -2000 5000
ON 48 ($30) -200 500 0 -200 500
-200.0 to 200.0C 1
OFF 17 ($11) -2000 2000 1 -2000 2000
ON 49 ($31) -200 200 0 -200 200
0.0 to 300.0C 2
OFF 18 ($12) 0 3000 1 0 3000
ON 50 ($32) 0 300 0 0 300
0.00 to 150.00C 3
OFF 19 ($13) 0 15000 2 0 15000
ON 51 ($33) 0 1500 1 0 1500
Pt100
-200.0 to 850.0C 4
OFF 20 ($14) -2000 8500 1 -2000 8500
ON 52 ($34) -200 850 0 -200 850
-200.0 to 500.0C 5
OFF 21 ($15) -2000 5000 1 -2000 5000
ON 53 ($35) -200 500 0 -200 500
-200.0 to 200.0C 6
OFF 22 ($16) -2000 2000 1 -2000 2000
ON 54 ($36) -200 200 0 -200 200
0.0 to 300.0C 7
OFF 23 ($17) 0 3000 1 0 3000
ON 55 ($37) 0 300 0 0 300
0.00 to 150.00C 8
OFF 24 ($18) 0 15000 2 0 15000
ON 56 ($38) 0 1500 1 0 1500
DC voltage
0-10mV 0.00 to 10.00 mV 9
ON
X
25 ($19) 0 1000 2 0 1000
0-100mV 0.0 to 100.0 mV A 26 ($1A) 0 1000 1 0 1000
0-1V 0.000 to 1.000 V B 27 ($1B) 0 1000 3 0 1000
0-5V 0.000 to 5.000 V D 29 ($1D) 0 5000 3 0 5000
1-5V 1.000 to 5.000 V E 30 ($1E) 1000 5000 3 1000 5000
0-10V 0.00 to 10.00 V F 31 ($1F) 0 1000 2 0 1000
*1: For thermocouples K, B, S, R, and W, the upper and lower input range limits may exceed their default values.
*2: Data stored in the internal memory is initialized to the hardware switch values when power is turned on. An ‘X’ symbol in the SW1-3
column indicates that the switch setting is ignored.
*3: “Software Setting” refers to values stored in data register IN. Any value not listed here is ignored.
*4: This is the factory setting. When ‘set by software’ is selected, the initial value of data register IN is ‘I: Thermocouple K’.