E1-9
IM 34M06H62-02E 2nd Edition : June 2008-00
Table E1.11 Operating Status
RUN.STUS
Bit
pos.
Symbol Description
1
14 1
12 11 10
4
210
0
RUN/STP 0: Sto
1: Run
1
UT
MAN 0: Automatic
1: Manual
2
CAS
1: Cascade
3
RMT/LOC 0: Remote
1: Local
4
EXPV/PV 0: Normal
1: External in
ut
5
EXOUT/OUT 0: Normal
1: External
out
ut
6
7
8
B.OUT 1: PVIN burnout
9
+OVER 1: PVIN +OVER
10
-OVER 1: PVIN
OVER
11
B.OUT 1: PV-burnout
12
+OVER 1: PV +OVER
13
OVER 1: PV
OVER
14
15
FUNC.ERR 1: Error detected
The data position number of RUN.STUS is 41 or 108 for loop1, 42 or 308 for loop2, 43 or 508 for loop3, and 44 or 708 for loop4.
Table E1.12 Alarm Status
ALM.STUS
Bit
pos.
Symbol Description
1
14 1
12 11 10
4
210
0
LM1
larm 1
enerated
1
LM2
larm 2
enerated
2
LM3
larm 3
enerated
3
LM4
larm 4
enerated
4
LMW1
larm 1 waitin
5
LMW2
larm 2 waitin
6
LMW3
larm 3 waitin
7
LMW4
larm 4 waitin
8
9
10
11
12
13
14
15
The data position number of ALM.STUS is 109 for loop1, 309 for loop2, 509 for loop3, or 709 for loop4.
Table E1.13 Error Status
ERR.STUS
Bit
pos.
Description
1
14 1
12 11 10
4
210
0
1
S
stem data error
2
Calibration value error
3
Controller or I/O
arameter error
4
O
eration
arameter error
5
D converter error
6
RJC error
7
EEPROM error
8
9
10
11
12
13
14
15
The data position number of ERR.STUS is 51 or 110 for loop1, 52 or 310 for loop2, 53 or 510 for loop3, and 54 or 710 for loop4.