1-137
IM 04L51B01-01EN
Configuring the GX/GP
1
Preset value
1
Setup Item Selectable Range or Options Default Value
Preset value –9.999999E+29 to 9.999999E+29
–9.9999999E+29 to –1.0000000E–30, 0,
1.0000000E-30 to 9.9999999E+29
0
1 Appears when On/Off is set to On.
Preset value
Set the preset value.
Watchdog timer
Setup Item Selectable Range or Options Default Value
On/Off Off, On Off
Timer
1
1 to 120 (s) 30
Value at timer-expired
1
Last value, Preset value Last value
1 Appears when the watchdog timer is set to On.
On/Off
Set this to On to use the watchdog timer.
Timer
Set the duration for monitoring values that fail to be updated.
If a value is not updated within the specified duration, the value is replaced.
Value at timer-expired
Set whether to set the value when the timer expires to the last value or preset value.
Explanation
Watchdog Timer Function
Data may fail to be updated due to Modbus or other communication problems.
The watchdog timer function replaces values with preset values or last values when values
are not updated within the specified duration (timer).
Data replacement occurs immediately when the timer expires, and the values are held until
the next read cycle.
Timer
Data not updated
Communication
channel data
A B C D E E E
Preset value: Z
Z
F G
Read cycle
Replace data
Communication data
H