5-7
IM 04L51B01-01EN
Maintenance and Troubleshooting
5
4
Tap Exit to exit from the Initialize Calibration screen.
Operation complete
Note
• Default password: default
• Initialization does not initialize the A/D calibration password.
If you forget the password, you will not be able to perform A/D calibration. Make sure you do not
forget the password.
5.1.4 Adjusting and Checking the Touch Screen
Path
GX/GP: MENU key > Browse tab > Initialize Calibration > menu Touch screen
calibration
Procedure
Adjusting and Checking
1
Tap Calibration + Confirmation.
2
Follow the instruction on the screen, and touch the crosshair with the supplied stylus
pen or the tip of a pen cap that is not sharp.
3
Follow the instruction on the screen, and check the adjustment result.
5.1 Maintenance