1-206
IM 04L51B01-01EN
Calibration correction settings
Set this to On to initialize calibration correction settings and calibration reminder settings (/
AH option).
Instruments tags, etc.
Set this to On to initialize instrument tag settings.
Setup Item Selectable Range or Options Default Value
Internal Data Off, On Off
Internal data
Set this to On to initialize all data in the internal memory.
Procedure
Initializing All Settings
1
Press MENU.
The menu screen appears.
2
Tap the Browse tab and then Initialize Calibration.
The menu screen appears.
3
Tap Initialize all under Initialize and then On.
4
Tap Execute.
A conrmation screen is displayed.
5
Tap OK.
The settings are initialized.
Operation complete
Note
• Before initializing, back up necessary setup parameters and other data.
Refer to page 1-196 in section 1.22.1, “Saving the Setting Parameters”
• Initialization does not initialize the A/D calibration password.
If you forget the password, you will not be able to perform A/D calibration. Make sure you do not
forget the password.
• When execute initialization, the message “Restart is required to reflect this changes. Continue?”
may appear. Tap OK, and the GX/GP will automatically restart with the specified language.
Initializing a Specific Item
1
Press MENU.
The menu screen appears.
2
Tap the Browse tab and then Initialize Calibration.
The menu screen appears.
3
Tap Initialize all under Initialize and then Off.
4
To initialize the security settings, tap Security settings and then On. Otherwise, tap
Off.
5
To initialize the settings other than the security settings, tap Other than Security
settings and then On. Otherwise, tap Off.
6
To initialize the data in the internal memory, tap Internal data and then On. Otherwise,
tap Off.
7
Tap Execute.
A conrmation screen is displayed.
1.25InitializingandCalibratingtheSystem(Initialization,reconfiguration,touchscreencalibration)