5
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation
GS 04L53B00-01EN
Safety and EMC Standards
• CSA:CSA22.2No.61010-1,installationcategory
II
*1
, pollution degree 2
*2
• UL:UL61010-1(CSANRTL/C)
• CE:
EMC directive
EN61326-1compliance,ClassATable2
EN61000-3-2compliance
EN61000-3-3compliance
EN55011 Class A Group 1
Low voltage directive
EN61010-1
Installation category II
*1
Pollution degree 2
*2
• EMCRegulatoryArrangementinAustraliaand
NewZealand(RCM):EN55011compliance,
Class A Group 1
• KCmarking:Electromagneticwaveinterference
preventionstandard,electromagneticwave
protectionstandardcompliance
*1 Installationcategory(overvoltagecategory)II:
Describesanumberwhichdenesatransient
overvoltage condition.
Impliestheregulationforimpulsewithstand
voltage.
“II”appliestoelectricalequipmentwhich
issuppliedfromthexedinstallationlikea
distribution board.
*2 Pollutiondegree2:
Describesthedegreetowhichasolid,liquid,
or gas which deteriorates dielectric strength or
surface resistivity is adhering.
“2”appliestonormalindooratmosphere.
Normally,onlynon-conductivepollutionoccurs.
• WEEEDirective:Compliant
Construction
• Frontpanel(terminal):Wateranddust-proof,
ComplieswithIEC529-IP20
• Material:Polycarbonate
• Color;
Front:Charcoalgreylight(CC28)
Bezel:Smokeblue(CC53)
• Dimensions:45.1mm(W)x111mm(H)x107.1
mm(D)(D:includingterminalcover)
• Weight:Approx.0.18kg
Power Supply
SuppyfromGX/GP,GX60expandableI/O,or
GM90PSpowersupplymodule.
• Powerconsumption:1.8Worless
External Dimensions
Unit: mm (approx. inch)
45.1(1.78)
107.1
3(0.12)
8(0.31)
100(3.94)
31.9
82.1(3.23)
Normal Operating Conditions
Fornormaloperatingconditionsofthismodule,
pleaserefertotheGeneralSpecicationsofthe
device (GX/GP, I/O Base Unit, or GM) that this
moduleismounted.
GXSpecications:GS04L51B01-01EN
GPSpecications;GS04L52B01-01EN
I/OBaseUnit(ExpandableI/O):ThisGeneral
Specications
GMSpecications:GS04L55B01-01EN
Transport and Storage Conditions
• Ambienttemperature:–25to70°C
• Ambienthumidity:5to95%RH(no
condensation)
• Vibration:10to60Hz,4.9m/s
2
maximum
• Shock:392m/s
2
maximum(inpackaged
condition)
Effects of Operating Conditions
None
Nov. 10, 2015-00