EasyManua.ls Logo

York XT AHU - FIGURE 18 - 25%;75% Sensing Option

York XT AHU
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
26
FORM 102.20-OM2
ISSUE DATE: 6/01/2015
SECTION 2 - START-UP AND OPERATION
The 25/75% Sensing option arrangement is similar to
the 25% Sensing (Min./Max.) option, but allows you
to measure airflow throughout the economizer cycle
also. In this arrangement, the 25% damper would be
for monitoring nominal airflow through the first 25%
down to 3.75% and the 75% damper would be for mon-
itoring the remaining 75%.
• 100% Sensing Option
The 100% sensing arrangement is a single damper de-
sign used to measure airflow throughout the full range
of the outside air damper down to 15% of nominal air-
flow.
FIGURE 18 - 25%/75% SENSING OPTION
LD17246
The 100% sensing option is the lowest cost option, but
should not be utilized when minimum airflow to be
sensed falls below 15% nominal flow. The 25% Sens-
ing (Min./Max.) and 100% Sensing option arrange-
ments will be the most prevalent.
The 100% Sensing arrangement with the outside and
return air dampers tied to a common actuator, will
usually be the most common configuration and cost-
effective solution. However, areas in which economiz-
er cycles are not often seen and operate primarily in
minimum outside air position, the 25% Sensing option
should be the preferred option for lowest airflow moni-
toring and a cost-effective solution.
In each of the available configurations, the minimum
airflow across the sensing portion of the airflow moni-
toring station is 300 FPM for the indoor AHU and 345
FPM for the outdoor AHU.
Factory Mounted Control Option
The AMS-60 airflow monitoring station may be or-
dered with or without Factory-mounted End Devices.
The Optional End Devices must be selected through
the YorkWorks program and consist of the following:
• Modulating, Spring Return Actuator(s)
• Low Pressure Transducer(s)
YorkWorks will provide all wiring schematics.
Jumper Selections
When selected, the AMS-60 factory provided trans-
ducers technically provides six (6) jumper selections
which allow you to select the appropriate range for
your application. However, only three (3) are appli-
cable to the AMS-60 function. The jumper selections
are as follows: 0-1", 0-.5", and 0-.25". These are field
adjustable. To determine the correct jumper setting for
your application, refer to the equation and examples on
Table 3 on page 27 for indoor AHUs and Table 4 on
page 28 for outdoor AHUs.
Input Power
A 24VAC power supply can be wired into the supply
voltage terminals on the Factory-mounted Actuator
and Transducer.
CFM Input Signal to Damper Actuator
2-10VDC (BELIMO)
0-10 VDC (JOHNSON CONTOLS)
CFM Output Signal from Transducer
0-10VDC
Sequence Of Operation
A 0-10 VDC or 2-10VDC control signal is sent to the
AMS 60 damper actuator from the Building Automa-
tion System (BAS). The BAS maintains the required
cfm by modulating the actuator on the control damper.
The BAS receives a 0-10 VDC signal back from the
transducer, confirming the cfm supplied. Upon loss of
power, the AMS-60 actuator returns to a closed posi-
tion.

Table of Contents

Related product manuals