2600T Series Pressure transmitters | OI/266/PB-EN Rev. E 39
11 Commissioning
— Condensed Status
Binary Code
Decimal
Code
Quality Sub-Status
0000 0000 0 BAD non specific
0010 10xx 40-43 BAD Process Related No Maintenance
0010 01xx 36-39 BAD
Maintenance Alarm More
Diagnostic Available
0011 11xx 60-63 BAD Function Check Local Override
0100 0000 64 UNCERTAIN non specific
0111 10xx 120-123 UNCERTAIN Process Related No Maintenance
0100 1011 75 UNCERTAIN
substitute value
– (FSAFE_TYPE = 0)
0100 1111 79 UNCERTAIN initial value (FSAFE_TYPE = 0)
0111 0011 115 UNCERTAIN Simulated value start
0111 01xx 116-119 UNCERTAIN Simulated value end
0110 00xx 96-99 UNCERTAIN simulated value
1000 0000 128 GOOD_NC ok
1000 0100 132 GOOD_NC Update Event
1000 1010 138 GOOD_NC Active Advisory Alarm high
1000 1110 142 GOOD_NC Active Critical Alarm high
1000 1001 137 GOOD_NC Active Advisory Alarm low
1000 1101 141 GOOD_NC Active Critical Alarm low
1010 01xx 164-167 GOOD_NC Maintenance Required
1010 10xx 168-171 GOOD_NC Maintenance Demanded
11.2.2 Device configuration
Operations on the transmitter like configuration/
parameterization, maintenance, monitoring are executed by
reading or writing the parameters mapped in the transmitter’s
blocks addressed as Slot/index. The Acyclic profibus
communication is used .
The DTM 266 PdP-PA is conform to the specifications FDT
1.2.1 and can be used within any FDTframeapplication/
configuration tool. The fdtFrameapplication tool from ABB is
the DAT200 (Asset Vision Basic) as freeware software tool.
Both the DTM and the DAT200 can be downloaded from the
ABB website www.abb.com.
Acyclic communication
The acyclic communications is executed only when a read or
write access at the device parameters is requested by the
operator from the Class 1 or Class 2 Masters. The device
parameters are addressed via SLOT/INDEX mapping. Refer to
the Appendix A to see the complete parameter mapping of the
266 PdP-PA.
Analog Input 1 setting
Damping
AI1_PV_FTIME
0 second
Output scale 0%
AI1_OUT_SCALE 0%
0.0
Output scale 100%
AI1_OUT_SCALE 100%
PTRB_SENSOR_LIM_HI
Output Scale Unit
AI1_OUT_SCALE Unit Code
Kpa
Critical Limit Low
AI1_LO_LO_LIM
AI1_OUT_SCALE 0%
– 10% of the SPAN
Advisory Limit Low
AI1_LO_LIM
Advisory Limit High
AI1_HI_LIM
AI1_OUT_SCALE 100%
+ 10% of the SPAN
Critical Limit High
AI1_HI_HI_LIM
Alarm Hysteresis
AI1_ALARM_HYS
0.5% of the SPAN
Fail Safe Type
AI1_FSAFE_TYPE
Last Usable Out Value
11.3 Factory settings
Transmitters are calibrated at the factory to the customer‘s
specified measuring range. The calibrated range and tag
number are provided on the name plate. If this data has not
been specified, the transmitter will be delivered with the
following configuration:
Parameter Factory setting
Node Address 126
TAG
PB_TAG_DESC
“PI000”
Calibration Lower Range Value 0%
PRTB_SCALE_IN 0%
0.0
Calibration Upper Range Value 100%
PRTB_SCALE_IN 100%
PTRB_SENSOR_LIM_HI
Calibration Unit
PRTB_SECONDARY_VALUE_1_UNIT
Kpa
Transfer function
PTRB_LIN_TYPE
Linear
Display Mode
HMI_MODE
One Line
Display Variable
HMI_LINE1
HMI_VARIABLE_1 = AI1_OUT

Table of Contents

Other manuals for ABB 2600T Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB 2600T Series and is the answer not in the manual?

ABB 2600T Series Specifications

General IconGeneral
BrandABB
Model2600T Series
CategoryTransmitter
LanguageEnglish

Related product manuals