2600T Series Pressure transmitters | OI/266/PB-EN Rev. E 67
Appendix A – Device mapping
Idx Parameter Data Type Size Storage Class Description Range Note
n+14 PILD_RETRAIN RW S U8 1 S
If YES, the PILD algorithm is forced to
train again when the process conditions
pass the maximum allowed deviation.
0 No
1 Yes
n+15 PILD_TRAIN_TIME RW S U8 1 S This parameter represents the duration of the training period
n+17 PILD_TRAIN_OUTPUT R S U8 1 D
This parameter gives information on the
status of the training phase
Bit 0: PILD TRAIN NOT DONE Training not yet executed
Bit 1: PILD TRAIN OK Training correct
Bit 2: PILD TRAIN FREQUENCY TUNING
The training phase is checking the signal frequency for
its execution
Bit 3: PILD TRAIN POWER INSTABLE
Signal power has passed the maximum allowed
deviation. This process condition is considered
instable for a good training
Bit 4: PILD TRAIN PRESSURE INSTABLE
Pressure has passed the maximum allowed deviation.
This process condition is considered instable for a
good training
Bit 5: PILD TRAIN LOW NOISE
The Noise of the process is too low for allowing a
good training
Bit 6: not used
Bit 7: not used
n+18 PILD_SENSITIVITY RW S U8 1 S Algorithm sensibility
1: LOWEST
2: VERY LOW
3: LOW
4: MEDIUM (Default)
5: HIGH
6: VERY HIGH
7: HIGHEST
n+19
PILD_BAND_
AUTOTUNING
RW S U8 1 S PILD auto tuning enable/disable
0 – No Doesn’t perform auto tune (default value)
1 – Yes Performs Auto Tune
n+20 PILD_BAND_LO RW S U8 1 S
Writable only if PILD_BAND_AUTOTUNING is set to 0
n+21 PILD_BAND_HI RW S U8 1 S
n+22 PWR_ON_CNT R S U16 2 D Power On Counter. Number of the device Power on
n+23 TOT_WORK_TIME R R 6 D Total Working hours. Time the transmitter has been kept switched on
n+24 PAR_WORK_TIME RW R 6 D
Partial Working hours. Partial amount of time the transmitter has been switched on.
An operator writing command can clear this counter.