Installation/start-up errors
AI1_OUT
Process Val
AI2_OUT
Static Press
AI3_OUT
Sensor temp
AI1_OUT
Process Val
AI2_OUT
Static Press
AI3_OUT
Sensor temp
Input
Simulation
Active
PdP
simulation
C088.030
The Pressure Value produced in output is
derived from a simulated input
BAD Function Check
Local Override
GOOD- OK
UNCERTAIN
Simulated Value
GOOD- OK
Static P
simulation
The Static PressureValue produced in
output is derived from a simulated input
GOOD-OK
BAD Function Check
Local Override
GOOD-OK GOOD-OK
UNCERTAIN
Sim. Value
GOOD-OK
Sensor Temp
simulation
The Sensor Temperature Value produced in
output is derived from a simulated input
GOOD-OK
BAD Function
Check Override
GOOD-OK
UNCERTAIN
Simulated Value
Replace Info M020.042
An element of the tx has been changed
(sensor or electronics). Replacement
operation must be executed.
GOOD Maintenance Demanded GOOD Maintenance Required
Process errors
AI1_OUT
Process Val
AI2_OUT
Static Press
AI3_OUT
Sensor temp
AI1_OUT
Process Val
AI2_OUT
Static Press
AI3_OUT
Sensor temp
Pressure Overrange F104.032
The Pressure is outside the overpressure
limit and risk to damage the sensor
BAD Mainten
Dia. Available
GOOD- OK BAD Sensor failure GOOD- OK
P-dP Out Of Limit F102.004
The Process Pressure is outside the sensor
limits and no longer representing the true
applied process value
BAD Process
Related No
Maintenance
GOOD- OK BAD Sensor failure GOOD- OK
Static Pressure Out Of Limit F100.005
The measured Static pressure is above its
operational limit
UNCERTAIN
No Maintenance
BAD Process Related
No Maintenance
GOOD- OK
UNCERTAIN Sens
Conv Not Accurate
BAD Sensor
failure
GOOD-OK
Sensor Temperature Out Of
Limit
S054.006
The measured sensor temperature is
outside of its operational limits
UNCERTAIN
Process Related No Maintenance
BAD Mainten.
Diag. Available
UNCERTAIN
Sensor Conversion Not Accurate
BAD Sensor failure
MWP Exceeded M052.031
The Static Pressure is higher than the
mechanical limit of process connection.
GOOD Maintenance Required GOOD Maintenance Required
Primary Variable Out of
Range
S050.010
Process value is outside its High or Low
working range
UNCERTAIN
No Maintenance
GOOD- OK
UNCERTAIN eng.
unit range violation
GOOD- OK
Static Pressure Out of Range S048.011
Static Pressure is outside its High or Low
working range
GOOD-OK
UNCERTAIN
No Maintenance
GOOD-OK GOOD-OK
UNCERTAIN
eng. unit
violation
GOOD-OK
PILD Output
PILD Affect
PV = FALSE
M018.038
The PILD algorithm has detected impulse
lines plugged. The Plugged Line can be one
among: High Side / Low Side / Both Sides /
One Undefined
GOOD Maintenance Required GOOD Maintenance Required
PILD Affect
PV = TRUE
BAD Maintenance Alarm More Diagnostic Available BAD – Sensor failure
PILD
Changed
Operating
Conditions
PILD Affect
PV = FALSE
M016.039
The pressure value currently detected is too
different from what used for the PILD
Training
GOOD Maintenance Required GOOD – Maintenance Required
PILD Affect
PV = TRUE
BAD Maintenance Alarm More Diagnostic Available BAD – Sensor failure