ACS 160 Users Manual 109
Note! Alarms (*) will not cause relay output RO1 (RO2) to activate when the relay output is
configured to indicate alarm condition in general. (Parameter 1401
RELAY OUTPUT 1 (1402
RELAY OUTPUT 2) has value 5 (ALARM) or 13 (FLT/ALARM)).
Note! Alarms (**) will be shown only if parameter 1608
DISPLAY ALARMS is set to 1 (YES)
25 Reserved.
26 **
OUTPUT OVERLOAD Inverter overload condition. The ACS 160 output current exceeds the ratings
given in Reference Section P.
27 *
AUTOMATIC RESET ACS 160 is about to perform automatic fault reset operation. As a result, the
drive may start after the reset operation. Refer to parameter group 31
AUTOMATIC RESET.
28 *
PID SLEEP PID sleep function is active. The drive may accelerate when PID sleep function
is deactivated. Refer to parameters 4018
SLEEP SELECTION, 4013 PID SLEEP
DELAY, 4014 PID SLEEP LEVEL and 4015 WAKE-UP LEVEL.
29 Reserved.
30 Reserved.
31
BR RES OVERLOAD Brake resistor is nearly overloaded. Refer to brake resistor instructions.