110 ACS 160 Users Manual
Table 9 Faults.
Fault Code Name
Description
1
OVERCURRENT Output current is excessive.
Motor load may be too high
Acceleration time may be too short (parameters 2201
ACCELER
TIME 1 and 2203 ACCELER TIME 2).
Motor or motor cable is faulty or connected wrong.
2
DC OVERVOLTAGE Intermediate circuit DC voltage is excessive.
Check mains for static or transient overvoltages
Deceleration time may be too short (parameters 2202
DECELER
TIME 1 and 2204 DECELER TIME 2)
Brake chopper (if present) may be underdimensioned
3
ACS160 OVERTEMP ACS 160 heat sink temperature is excessive. Temperature trip limit is
105 °C.
Check air flow and fan operation.
Check motor power against unit power.
4 **
SHORT CIRCUIT Fault current. Possible reasons for this fault are:
There is a short-circuit in the motor cable(s) or motor
Supply disturbances
5
OUTPUT OVERLOAD Inverter overload condition. The ACS 160 output current exceeds the
ratings given in Reference Section P.
6
DC UNDERVOLTAGE Intermediate circuit DC voltage is not sufficient.
Mains phase may be missing
Fuse may be blown
7
ANALOGUE INPUT 1 Analogue input 1 loss. Analogue input value is less than MINIMUM AI1
(1301). See also parameter 3001
AI<MIN FUNCTION.
8
ANALOGUE INPUT 2 Analogue input 2 loss. Analogue input value is less than MINIMUM AI2
(1306). See also parameter 3001
AI<MIN FUNCTION.
9
MOTOR OVERTEMP Motor overtemperature condition as estimated by the ACS 160. Refer to
parameters 3004 3008.
10
PANEL LOSS Panel communication loss. Control panel is disconnected when the
drive is receiving start, stop and direction commands from the panel.
- Drive is in local control mode (LOC is shown in the control panel
display), or
- Drive is in remote control mode (REM is shown) and is parameterised
to accept start/stop, direction or reference from the panel. Refer to
parameters in groups 10 COMMAND INPUTS and 11 REFERENCE
SELECT.
See also parameter 3002
PANEL LOSS.
11
PARAMETERING Parameter values are inconsistent:
MINIMUM AI1 > MAXIMUM AI1 (parameters 1301, 1302)
MINIMUM AI2 > MAXIMUM AI2 (parameters 1304, 1305)
MINIMUM FREQ > MAXIMUM FREQ (parameters 2007, 2008)
12
MOTOR STALL Motor stall. This may be caused by excessive load or insufficient motor
power. Refer to parameters 3009 3012.
13
SERIAL COMM LOSS Serial communication through Standard Modbus Channel is lost.
Check connections between external control system and the
ACS 160.
Refer to parameters 5204
COMM FAULT TIME and 5205 COMM FAULT
FUNC.
14
EXTERNAL FAULT SIGNAL External fault is active. See parameter 3003 EXTERNAL FAULT.
15 **
OUTPUT EARTH FAULT Earth fault. The load on the incoming mains system is out of balance.
There may be a fault in the motor or motor cable.
Motor cable may be too long.
16 **
DC BUS RIPPLE Ripple voltages on the DC bus are too large.
Mains phase may be missing
Fuse may be blown