ABB ACS320 - Sleep Function for the Process PID (PID1) Control

ABB ACS320
442 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Program features 125
Sleep function for the process PID (PID1) control
The sleep function operates on a 2 ms time level.
The block diagram below illustrates the sleep function enable/disable logic. The sleep
function can be put into use only when the PID control is active.
1) 1 = Activate sleeping
0 = Deactivate sleeping
4022
SelectCompare
1<2
Or
<1
4024
Delay
t
1
2
4023
NOT SEL
DI1
And
&
%refActive
PIDCtrlActive
modulating
Set/Reset
S
R
S/R
NOT SEL
INTERNAL
DI1
4026
Delay
t
Or
<1
StartRq
5320 (B1)
5320 (B2)
1)
INTERNAL
4022
Select
Mot. speed: Actual speed of the motor
%refActive: The % reference (EXT REF2) is in use. See parameter 1102.
PIDCtrlActive: 9902 is PID CTRL.
modulating: The inverter IGBT control is operating.
.
.
.
.
.
.
Compare
1>2
1
2
Output
freq.
0132
4025
4030
Delay
t
Or
<1
Set/Reset
S
R
S/R
2)
2) 1 = Activate sleep boost
0 = Deactivate sleep boost