Actual signals and parameters 279
Default values with different macros
When application macro is changed (9902 APPLIC MACRO), the software updates
the parameter values to their default values. The table below shows the parameter
default values for different macros. For other parameters, the default values are the
same for all macros. See the parameter list starting on page 148.
Index Name/
Selection
HVAC
DEFAULT
SUPPLY FAN RETURN FAN CLNG TWR
FAN
CONDENSER BOOSTER
PUMP
PUMP
ALTERNA
9902 APPLIC
MACRO
1 = HVAC
DEFAULT
2 = SUPPLY
FAN
3 = RETURN
FAN
4 = CLNG
TWR FAN
5 =
CONDENSER
6 =
BOOSTER
PUMP
7 = PUMP
ALTERNA
1001 EXT1
COMMANDS
1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1
1002 EXT2
COMMANDS
1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1
1003 DIRECTION 1 =
FORWARD
1 =
FORWARD
1 = FORWARD 1 =
FORWARD
1 = FORWARD 1 = FORWARD 1 = FORWARD
1102 EXT1/EXT2
SEL
0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1
1103 REF1 SELECT 1 = AI1 1 = AI1 1 = AI1 1 = AI1 1 = AI1 1 = AI1 1 = AI1
1106 REF2 SELECT 19 =
PID1OUT
19 =
PID1OUT
19 = PID1OUT 19 =
PID1OUT
19 = PID1OUT 19 =
PID1OUT
19 =
PID1OUT
1201 CONST
SPEED SEL
3 = DI3 3 = DI3 3 = DI3 3 = DI3 3 = DI3 3 = DI3 0 = NOT SEL
1304 MINIMUM AI2 20.0% 20.0% 20.0% 20.0% 20.0% 20.0% 20.0%
1401 RELAY
OUTPUT 1
1 = READY 7 =
STARTED
7 = STARTED 1 = READY 1 = READY 1 = READY 31 = PFA
1601 RUN ENABLE 0 = NOT SEL 2 = DI2 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL
1805 DO SIGNAL 2 = RUN 2 = RUN 2 = RUN 2 = RUN 2 = RUN 2 = RUN 2 = RUN
2008 MAXIMUM
FREQ
50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz
2201 ACC/DEC 1/2
SEL
0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL
2202 ACCELER
TIME 1
30.0 s 30.0 s 30.0 s 30.0 s 30.0 s 10.0 s 10.0 s
2203 DECELER
TIME 1
30.0 s 30.0 s 30.0 s 30.0 s 30.0 s 10.0 s 10.0 s
3019 COMM FAULT
TIME
10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s
4001 GAIN 2.5 2.5 2.5 2.5 2.5 2.5 2.5
4002 INTEGRATION
TIME
3.0s 3.0s 3.0s 3.0s 3.0s 3.0s 3.0s
4101 GAIN 2.5 2.5 2.5 2.5 2.5 2.5 2.5
4102 INTEGRATION
TIME
3.0s 3.0s 3.0s 3.0s 60.0s 3.0s 3.0s
8116 AUX MOT
STOP D
3.0s 3.0s 3.0s 3.0s 3.0s 3.0s 3.0s
8118 AUTOCHNG
INTERV
0.0 =
NOT SEL
0.0 =
NOT SEL
0.0 =
NOT SEL
0.0 =
NOT SEL
0.0 =
NOT SEL
0.0 =
NOT SEL
0.0 =
NOT SEL
8123 PFA ENABLE 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 1 = ACTIVE