EasyManua.ls Logo

ABB ACS320 - Max Master Property; MSTP Token Counter; Bacnet Protocol Implementation Conformance Statement

ABB ACS320
442 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fieldbus control 333
Max Master Property
Configure the Device Object Max Master property using drive parameter 5313.
Default: 5313 = 127.
MS/TP Token Counter
Parameter 5316 stores the count of MS/TP tokens passed to the associated node.
BACnet protocol implementation conformance statement
This statement is part of this standard and is required for its use.
Date: December 2015
Vendor Name: ABB, Inc
Product Name: Low Voltage AC Motor Drive
Product Model Number: ACS320-xxE (European regional variant)
ACS320-xxU (USA regional variant)
Applications Software Version: 403C (European regional variant)
4050 (USA regional variant)
Firmware Revision: 0528
BACnet Protocol Revision: 7
Product Description: The ACS320 is a high-performance adjustable frequency
drive specifically designed for commercial automation
applications. This product supports native BACnet,
connecting directly to the MS/TP LAN. All standard
MS/TP baud rates are supported, as well as master
mode functionality. Over BACnet, the drive can be fully
controlled as a standard adjustable frequency drive. In
addition, up to 13 configurable I/O ports are available
over BACnet for user application.
BACnet Standardized Device
Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
List all BACnet Interoperability
Building Blocks Supported
(Annex K):
DS-RP-B, DS-WP-B, DM-DDB-B, DM-DOB-B,
DM-DCC-B, DM-RD-B.