294 Fieldbus control
Miscellaneous drive control
Note: The user should change only the parameters for the functions you wish to
control vial fieldbus. All other parameters should typically remain at factory default.
For simple start/stop and speed reference fieldbus control, only parameters 1001
EXT1 COMMANDS and 1103 REF1 SELECT need to be changed to COMM.
Using the fieldbus for miscellaneous drive control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
1.ABB recommends hard wiring run permissive and safeties.
Drive Parameter Value Setting
Protocol Reference
Modbus
N2 FLN BACnet
abb drv
dcu
profile
1601 RUN
ENABLE
7
(COMM)
Run enable by
fieldbus. (Not
recommended
1
)
40001
bit 3
40031
bit 6
(inverted)
BO4 35 BV12
1604 FAULT
RESET
SEL
8
(COMM)
Fault reset by
fieldbus.
40001
bit 7
40031
bit 4
BO6 94 BV14
1606 LOCAL
LOCK
8
(COMM)
Source for local
lock selection is the
fieldbus.
Does not
apply
40031
bit 14
1607 PARAM
SAVE
1 (SAVE) Saves altered
parameters to
memory (then
value returns to 0).
41607 41607 BO18 N/A
1
1608 START
ENABLE
1
7
(COMM)
Source for start
enable 1 is the
fieldbus Command
word. (Not
recommended)
1
Does not
apply.
40032
bit 2
BV20
1609 START
ENABLE
2
7
(COMM)
Source for start
enable 2 is the
fieldbus Command
word. (Not
recommended)
1
40032
bit 3
BV21
2201 ACC/DEC
1/2 SEL
7
(COMM)
Source for ramp
pair selection is the
fieldbus.
40031
bit 10