Actual signals and parameters 155
Group 03: FB actual signals
This group monitors fieldbus communications.
Group 03: FB actual signals
Code Description Range Resolution Default S
0301
FB CMD WORD 1
---
Read-only copy of the Fieldbus command word 1.
The fieldbus command is the principal means for controlling the drive from a
fieldbus controller. The command consists of two Command words. Bit-coded
instructions in the Command words switch the drive between states.
To control the drive, using the Command words, an external location (EXT1 or
EXT2) must be active and set to COMM. (See parameters 1001 EXT1 COMMANDS
and 1002 EXT2 COMMANDS.)
The control panel displays the word in hex. For example, all zeros and a 1 in Bit 0
displays as 0001. All zeros and a 1 in BIt 15 displays as 8000.
0302
FB CMD WORD 2
---
Read-only copy of the Fieldbus command word 2.
See parameter 0301 FB CMD WORD 1.
Bit # 0301 FB CMD WORD 1 0302 FB CMD WORD 2
0 STOP FBLOCAL_CTL
1 START FBLOCAL_REF
2 REVERSE START_DISABLE1
3 LOCAL START_DISABLE2
4 RESET Reserved
5EXT2 Reserved
6 RUN_DISABLE MOTOR_HEAT
7 STPMODE_R Reserved
8 STPMODE_EM Reserved
9 STPMODE_C Reserved
10 RAMP_2 Reserved
11 RAMP_OUT_0 REF_CONST
12 RAMP_HOLD REF_AVE
13 RAMP_IN_0 LINK_ON
14 REQ_LOCALLOC REQ_STARTINH
15 Reserved OFF_INTERLOCK