202 Actual signals and parameters
Group 29: Maintenance trig
This group contains usage levels and trigger points. When usage reaches the set
trigger point, a notice is displayed on the control panel signals that maintenance is
due.
Group 29: Maintenance trig
Code Description Range Resolution Default S
2901
COOLING FAN TRIG
0.0 … 6553.5 kh 0.1 kh 0.0
Defines the trigger point for the drive cooling fan run time counter. Value is compared
to parameter 2902 COOLING FAN ACT.
• Time. If parameter value is set to zero, the trigger is disabled.
0.0 = NOT SEL
2902
COOLING FAN ACT
0.0 … 6553.5 kh 0.1 kh 0.0
Defines the actual value for the cooling fan run time counter. When parameter 2901
COOLING FAN TRIG has been set to a non zero value, the counter starts. When the
actual value of the counter exceeds the value defined by parameter 2901, a
maintenance notice is displayed on the panel.
• Time. Parameter is reset by writing 0.0 to it.
2903
REVOLUTION TRIG
0 … 65535 MRev 1 MRev 0
Defines the trigger point for the motor revolution counter. Value is compared to
parameter 2904 REVOLUTION ACT value.
• Millions of revolutions. If parameter value is set to zero, the trigger is disabled.
0.0 = NOT SEL
2904
REVOLUTION ACT
0 … 65535 MRev 1 MRev 0
Defines the actual value for the motor revolution counter. When parameter 2903
REVOLUTION TRIG has been set to a non zero value, the counter starts. When the
actual value of the counter exceeds the value defined by parameter 2903, a
maintenance notice is displayed on the panel.
• Millions of revolutions. Parameter is reset by setting it to zero.
2905
RUN TIME TRIG
0.0 … 6553.5 kh 0.1 kh 0.0
Defines the trigger point for the drive run time counter. Value is compared to the value
of parameter 2906 RUN TIME ACT.
• Time. If parameter value is set to zero, the trigger is disabled.
0.0 = NOT SEL
2906
RUN TIME ACT
0.0 … 6553.5 kh 0.1 kh 0.0
Defines the actual value for the drive run time counter. When parameter 2905 RUN
TIME TRIG has been set to a non zero value, the counter starts. When the actual
value of the counter exceeds the value defined by parameter 2905, a maintenance
notice is displayed on the panel.
• Time. Parameter is reset by setting it to zero.