334 Fieldbus control
Standard Object Types
Supported:
Object instantiation is static, that is objects cannot be
created or deleted.
See Object/Property support matrix tables from
page 335.
Data Link Layer Options: BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, EIA-485 ARCNET (Clause 8), baud
rate(s) ___
MS/TP master (Clause 9), baud rate(s): 9600, 19200,
38400, 76800
MS/TP slave (Clause 9), baud rate(s): 9600, 19200,
38400, 76800
Point-To-Point, EIA 232 (Clause 10), baud rate(s): ___
Point-To-Point, modem, (Clause 10), baud rate(s): ___
LonTalk, (Clause 11), medium: __________
Other: __________
Device Address Binding:
Is static device binding
supported? (This is currently
necessary for two-way
communication with MS/TP
slaves and certain other
devices.)
Yes
No
Networking Options: Router, Clause 6 - List all routing configurations,
eg, ARCNET-Ethernet, Ethernet-MS/TP, etc.
Annex H, BACnet Tunneling Router over IP
BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign
Devices? Yes No
Character Sets Supported:
Indicating support for multiple
character sets does not imply
that they can all be supported
simultaneously.
ANSI X3.4
IBM™/Microsoft™ DBCS
ISO 8859-1
ISO 10646 (UCS-2)
ISO 10646 (UCS-4)
JIS C 6226
If this product is a
communication gateway,
describe the types of non-
BACnet equipment/network(s)
that the gateway supports: