280 Actual signals and parameters
Index Nam e/
Selection
INT TIMER INT TIMER CS FLOATING
PNT
DUAL
SETPPID
DL SP PID CS E-BYPASS HAND
CONTROL
9902 APPLIC
MACRO
8 = INT TIMER 9 = INT
TIMER CS
10 =
FLOATING
PNT
11 = DUAL
SETPPID
12 = DL SP
PID CS
13 = BYPASS 14 = HAND
CONTROL
1001 EXT1
COMMANDS
11 = TIMER
1
1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1 0 = NOT SEL
1002 EXT2
COMMANDS
1 = TIMER 1 0 = NOT SEL 1 = DI1 1 = DI1 1 = DI1 1 = DI1 0 = NOT SEL
1003 DIRECTION 1 = FORWARD 1 = FORWARD 1 = FORWARD 1 = FORWARD 1 = FORWARD 1 = FORWARD 1 = FORWARD
1102 EXT1/EXT2
SEL
0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1 2 = DI2 0 = EXT1 0 = EXT1
1103 REF1 SELECT 1 = AI1 0 = KEYPAD 30 =
DI4U,5D
1 = AI1 1 = AI1 1 = AI1 1 = AI1
1106 REF2 SELECT 19 =
PID1OUT
2 = AI2 19 =
PID1OUT
19 =
PID1OUT
19 =
PID1OUT
19 = PID1OUT 2 = AI2
1201 CONST
SPEED SEL
0 = NOT SEL 15 = TIMER
1
3 = DI3 0 = NOT SEL 10 = DI4,5 0 = NOT SEL 0 = NOT SEL
1304 MINIMUM AI2 20.0% 20% 20% 20.0% 20.0% 20.0% 20.0%
1401 RELAY
OUTPUT 1
7 =
STARTED
7 = STARTED 7 = STARTED 7 = STARTED 1 = READY 7 = STARTED 1 = READY
1601 RUN ENABLE 2 = DI2 2 = DI2 2 = DI2 2 = DI2 0 = NOT SEL 2 = DI2 0 = NOT SEL
1805 DO SIGNAL 2 = RUN 2 = RUN 2 = RUN 2 = RUN 2 = RUN 2 = RUN 2 = RUN
2008 MAXIMUM
FREQ
50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz
2201 ACC/DEC 1/2
SEL
0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL
2202 ACCELER
TIME 1
30.0 s 30.0 s 30.0 s 30.0 s 30.0 s 30.0 s 30.0 s
2203 DECELER
TIME 1
30.0 s 30.0 s 30.0 s 30.0 s 30.0 s 30.0 s 30.0 s
3019 COMM FAULT
TIME
10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s
4001 GAIN 2.5 1.0 2.5 2.5 2.5 2.5 1.0
4002 INTEGRATION
TIME
3.0 s 60.0 s 3.0 s 3.0 s 3.0 s 3.0 s 60.0 s
4101 GAIN 2.5 2.5 2.5 2.5 2.5 2.5 2.5
4102 INTEGRATION
TIME
3.0 s 3.0 s 3.0 s 3.0 s 3.0 s 3.0 s 3.0 s
8116 AUX MOT
STOP D
3.0 s 3.0 s 3.0 s 3.0 s 3.0 s 3.0 s 3.0 s
8118 AUTOCHNG
INTERV
0.0 =
NOT SEL
0.0 = NOT
SEL
0.0 = NOT
SEL
0.0 = NOT
SEL
0.0 = NOT
SEL
0.0 = NOT SEL 0.0 = NOT
SEL
8123 PFA ENABLE 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL