Actual signals and parameters 265
8113
LOW FREQ 2
0.0 500.0 Hz 0.1 Hz 25.0
Sets the frequency limit used to stop the second auxiliary motor.
•See 8112 LOW FREQ 1 for a complete description of the operation.
The second auxiliary motor stops if:
Two auxiliary motors are running.
Drive output frequency drops below the limit: 8113 LOW FREQ 2 - 1.
Output frequency stays below the relaxed limit (8113 LOW FREQ 2 + 1 Hz) for at
least the time: 8116 AUX MOT STOP D.
8114
LOW FREQ 3
0.0 500.0 Hz 0.1 Hz 25.0
Sets the frequency limit used to stop the third auxiliary motor.
•See 8112 LOW FREQ 1 for a complete description of the operation.
The third auxiliary motor stops if:
Three auxiliary motors are running.
ACS320 output frequency drops below the limit: 8114 LOW FREQ 3 - 1.
Output frequency stays below the relaxed limit (8114 LOW FREQ 3 + 1 Hz) for at
least the time: 8116 AUX MOT STOP D.
8115
AUX MOT START D
0.0 … 3600.0 s 0.1 s; 1 s 5.0 s
Sets the Start delay for the auxiliary motors.
The output frequency must remain above the start frequency limit (parameter 8109,
8110, or 8 111) for this time period before the auxiliary motor starts.
•See 8109 START FREQ 1 for a complete description of the operation.
8116
AUX MOT STOP D
0.0 … 3600.0 s 0.1 s; 1 s 3.0 s
Sets the Stop delay for the auxiliary motors.
The output frequency must remain below the low frequency limit (parameter 8112,
8113, or 8114) for this time period before the auxiliary motor stops.
•See 8112 LOW FREQ 1 for a complete description of the operation.
Group 81: PFA control