Fieldbus control 327
BV14 FAULT RESET Command to reset a fault
(drive must be configured
for BACnet control).
RESET/NO C
BV15 MBOX READ Command to read
parameter specified by
AV25, MBOX PARAM. The
parameter value is returned
in AV26, MBOX DATA.
READ/RESET W
BV16 MBOX WRITE Command to write data
value specified by AV26,
MBOX DATA, to the
parameter value specified
by AV25, MBOX PARAM.
WRITE/RESET W
BV17 LOCK PANEL Command to lock the panel
and prevent parameter
changes.
LOCK/UNLOCK W
BV18 CTL OVERRIDE
CMD
Commands the drive into
BACnet Control Override. In
this mode, BACnet acquires
drive control from its normal
source. Note that the HAND
mode of the panel has
priority over BACnet Control
Override.
ON/OFF C
BV19 CTL OVERRIDE
ACT
Indicates if drive is placed in
BACnet Control Override by
commanding BV18. In this
mode, BACnet acquires
drive control from its normal
source. Note that HAND
mode of the panel has
priority over BACnet control
Override.
ON/OFF R
BV20 START ENABLE
1
Command to assert Start
Enable1 (drive must be
configured for BACnet
control).
ENABLE/DISABLE C
BV21 START ENABLE
2
Command to assert Start
Enable 2 (drive must be
configured for BACnet
control).
ENABLE/DISABLE C
Instance
ID
Object Name Description
Active/Inactive
Text
Present Value
Access Type