390 Technical data
03x-15A6-4 35 15 35 R3 18.0 MS165-20
3)
--
03x-23A1-4 50 20 50 R3 26.0 MS165-32
3)
--
03x-31A0-4 80 25 80 R4 43.0 MS165-54
3)
--
03x-38A0-4 100 30 100 R4 51.0 MS165-65
3)
--
03x-44A0-4 100 35 100 R4 56.0 MS165-65
3)
--
00578903.xls.J
1)
E = EMC filter connected (metal EMC filter screw installed),
U = EMC filter disconnected (plastic EMC filter screw installed), U.S parameterization.
2)
minimum fuse size can be used with input choke according to table in Rating section
3)
Trip class 10; integral trip indication; does not require additional line-side feeder terminal.
4)
For all drives, the enclosure must be sized to accommodate the specific thermal considerations of the
applications as well as provide free space for cooling. See section, Free space requirements on page 392.
For UL only: The minimum enclosure volume is specified in the UL listing for drive frames R0 and R1 when
applied with the ABB type E MMP shown in the table. ACS320 drives are intended to be mounted in an
enclosure unless a NEMA 1 kit is added.
Type Fuses MMPs
ACS320- gG UL Class T or
CC (600 V)
Frame I
1N
MMP Type E
Min. Encl.
Vol.
4)
x = E/U
1)
A min A
2)
max A A dm
3
in
3