Fault tracing 351
1017 PAR SETUP 1
(6320)
0307 bit 15
Only two of the
following can be used
simultaneously:
MTAC-01 encoder
module, frequency
input signal or
frequency output
signal.
Disable frequency output, frequency
input or encoder:
• change transistor output to digital
mode (value of parameter 1804 TO
MODE = 0 [DIGITAL]), or
• change frequency input selection to
other value in parameter groups
11 REFERENCE SELECT,
40 PROCESS PID SET 1,
41 PROCESS PID SET 2 and
42 EXT / TRIM PID, or
• disable (parameter 5002
ENCODER ENABLE) and remove
MTAC-01 encoder module.
CODE FAULT CAUSE WHAT TO DO