EasyManua.ls Logo

ABB ACS355 - Parameter Mode

ABB ACS355
406 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
82 Control panels
Parameter mode
In the Parameter mode, you can:
view and change parameter values
select and modify the signals shown in the Output mode
start, stop, change the direction and switch between local and remote control.
How to select a parameter and change its value
Step Action Display
1. Go to the Main menu by pressing if you are in
the Output mode, otherwise by pressing
repeatedly until you see MENU at the bottom.
2. If the panel is not in the Parameter mode (“PAr” not
visible), press key or until you see “PAr”
and then press . The display shows the number
of one of the parameter groups.
3. Use keys and to find the desired
parameter group.
4. Press . The display shows one of the
parameters in the selected group.
5. Use keys and to find the desired
parameter.
6. Press and hold for about two seconds until the
display shows the value of the parameter with
underneath indicating that changing of the value is
now possible.
Note: When is visible, pressing keys and
simultaneously changes the displayed value to
the default value of the parameter.
7. Use keys and to select the parameter
value. When you have changed the parameter value,
starts flashing.
To save the displayed parameter value, press
.
To cancel the new value and keep the original,
press .
LOC
MENU FWD
rEF
LOC
MENU FWD
PAr
LOC
PAR FWD
-01-
LOC
PAR FWD
-11-
LOC
PAR FWD
1101
LOC
PAR FWD
1103
SET
SET
LOC
PAR SET FWD
1
SET
LOC
PAR SET FWD
2
LOC
PAR FWD
1103

Table of Contents

Other manuals for ABB ACS355

Related product manuals