176 Actual signals and parameters
Fieldbus equivalent
Example: If 2017 MAX TORQUE 1 (see page 217) is set from an external control
system, an integer value of 1000 corresponds to 100.0%. All the read and sent values
are limited to 16 bits (-32768…32767).
Default values with different macros
When application macro is changed (parameter 9902 APPLIC MACRO), the software
updates the parameter values to their default values. The table below shows the
parameter default values for different macros. For other parameters, the default
values are the same for all macros (shown in the parameter list starting on page 185).
Note: It is possible to control several functions with one input (DI or AI), and there is a
chance of mismatch between these functions. In some cases it is desired to control
several functions with one input.
For example in the ABB standard macro, DI3 and DI4 are set to control constant
speeds. On the other hand, it is possible to select value 6 (DI3U,4D) for parameter
Index Name/
Selection
ABB
STANDARD
3-WIRE ALTERNA
TE
MOTOR
POT
HAND/
AUTO
PID
CONTROL
TORQUE
CONTROL
9902 APPLIC
MACRO
1 =
ABB
STANDARD
2 =
3-WIRE
3=
ALTERNAT
E
4 =
MOTOR
POT
5 =
HAND/AUT
O
6 =
PID
CONTROL
7 =
TORQUE
CTRL
1001 EXT1
COMMANDS
2 = DI1,2 4 =
DI1P,2P,3
9 = DI1F,2R 2 = DI1,2 2 = DI1,2 1 = DI1 2 = DI1,2
1002 EXT2
COMMANDS
0 = NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
21 = DI5,4 20 = DI5 2 = DI1,2
1003 DIRECTION 3 =
REQUEST
3 =
REQUEST
3 =
REQUEST
3 =
REQUEST
3 =
REQUEST
1 =
FORWARD
3 =
REQUEST
1102 EXT1/EXT2
SEL
0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1 3 = DI3 2 = DI2
3 = DI3
1103 REF1 SELECT 1 = AI1 1 = AI1 1 = AI1 12 =
DI3U,4D(N
C)
1 = AI1 1 = AI1 1 = AI1
1106 REF2 SELECT 2 = AI2 2 = AI2 2 = AI2 2 = AI2 2 = AI2 19 =
PID1OUT
2 = AI2
1201 CONST
SPEED SEL
9 = DI3,4 10 = DI4,5 9 = DI3,4 5 = DI5 0 = NOT
SEL
3 = DI3 4 = DI4
1304 MINIMUM AI2 1.0% 1.0% 1.0% 1.0% 20.0% 20.0% 20.0%
1501 AO1
CONTENT SEL
103 102 102 102 102 102 102
1601 RUN ENABLE 0 = NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
4 = DI4 0 = NOT
SEL
2201 ACC/DEC 1/2
SEL
5 = DI5 0 = NOT
SEL
5 = DI5 0 = NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
5 = DI5
3201 SUPERV 1
PARAM
103 102 102 102 102 102 102
3401 SIGNAL1
PARAM
103 102 102 102 102 102 102
9904 MOTOR CTRL
MODE
3 =
SCALAR:
FREQ
1 =
VECTOR:
SPEED
1 =
VECTOR:
SPEED
1 =
VECTOR:
SPEED
1 =
VECTOR:
SPEED
1 =
VECTOR:
SPEED
2 =
VECTOR:
TORQ