Supply modules. The drawing shows the configuration of a diode supply unit with two modules,
ie. there is a common air-to-liquid exchanger in the cubicle. With an IGBT supply unit, each
module has a dedicated air-to-liquid exchanger as shown for item 2.
1
Inverter modules2
To/From cooling unit3
Air-to-liquid heat exchangerA/L
Heat sinkHS
Inlet valvea
Inlet-side drain valveb
Outlet valvec
Outlet-side drain valved
The coolant used with ACS880 liquid-cooled drive systems is Antifrogen® L 25% or
50% mixture. See Coolant specification (page 120).
116 Internal cooling circuit