Heavy overload useShort time overload use
Frame
ACS880-
1607LC-…
P
Hd
I
Hd
P
short time
I
short time
kWAkWA
92910587688742×R8i1400A-7
106212098789992×R8i1600A-7
1195136098711242×R8i1800A-7
Nominal supply voltage of the drive
U
n
Maximum continuous DC input current from DC bus
I
DC input
Maximum continuous output current to/from energy storage
I
rms output
Maximum continuous output power to/from energy storage
P
contmax
Maximum output current to/from energy storage. Available for 10 seconds at start, otherwise
as long as permitted by drive temperature.
I
max output
Nominal apparent power
S
n
Peak-to-peak value of output current ripple measured after the filter
I
p2p
Switching frequency at output terminals (energy storage connection) measured after the
filter
f
sw out
Continuous output current allowing 10 s of
I
max output
every 60 s
I
short time
10 s 50 s
60 s
I
max output
I
short time
Continuous output power allowing 10 s of
I
max output
every 60 s
P
short time
Continuous output current allowing 150%
I
Hd
for 1 min every 5 min
I
Hd
150% I
Hd
I
Hd
1 min 4 min
5 min
Continuous output power allowing 150%
I
Hd
for 1 min every 5 min
P
Hd
■
Derating
Surrounding air temperature derating
In the temperature range +45…55 °C (+113…131 °F), the rated output current is derated
by 0.5 percentage points for every added 1 °C (1.8 °F). The output current can be
calculated by multiplying the current given in the rating table by the derating factor
(k)
:
Technical data 125