Default I/O diagram of the converter control unit (BCU)
The diagram below shows the default I/O connections of the BCU control unit of the
converter, and describes the use of the signals/connections. Under normal
circumstances, the factory-made wiring should not be changed.
The wire size accepted by all screw terminals (for both stranded and solid wire) is
0.5 2.5 mm
2
(22 12 AWG). The tightening torque is 0.45 N·m (4 lbf·in).
DescriptionTerminal
Drive-to-drive linkXD2D
Not in use by default
B1
1
2
3
4
A2
BGND3
Shield4
Drive-to-drive link termination switch
1)
D2D.TERM
ON
OFF
RS485 connectionX485
CIO-01 module connection (optional)
B5
5
6
7
8
A6
BGND7
Shield8
Relay outputsXRO1, XRO2, XRO3
XRO1: Not in use
250 V AC / 30 V DC, 2 A
Norm. closedNC11
22
23
31
32
11
12
13
21
33
CommonCOM12
Norm. openNO13
XRO2: Fault (-1)
2)
(Energized = no fault)
250 V AC / 30 V DC, 2 A
Norm. closedNC21
CommonCOM22
Norm. openNO23
XRO3: Fan control (DC/DC converter
running, fan control on)
250 V AC / 30 V DC, 2 A
Norm. closedNC31
CommonCOM32
Norm. openNO33
Safe torque offXSTO, XSTO OUT
XSTO: Factory connection. Both circuits (power module, control unit) must
be closed for the unit to start (IN1 and IN2 must be connected to OUT).
3)
OUT1
5
6
7
8
1
2
3
4
SGND2
IN13
IN24
XSTO OUT: Not in use
IN15
SGND6
IN27
SGND8
The control unit 69