DescriptionTerminal
Memory unit connectionX205
1)
Must be set to ON when the unit is the first or last unit on the drive-to-drive (D2D) link. On intermediate units, set
termination to OFF.
2)
Default use of the signal in the control program. The use can be changed by a parameter. See also the delivery-specific
circuit diagrams.
3)
This input only acts as a true Safe torque off input in inverter units. In other applications (eg, supply, DC/DC
converter, or brake unit), de-energizing the IN1 and/or IN2 terminal will stop the unit but not constitute a true safety
function.
4)
Total load capacity of these outputs is 4.8 W (200 mA at 24 V) minus the power taken by DIO1 and DIO2.
5)
Determines whether DICOM is separated from DIOGND (ie, common reference for digital inputs floats). ON: DICOM
connected to DIOGND. OFF: DICOM and DIOGND separate.
6)
Current [0(4)…20 mA,
R
in
= 100 ohm] or voltage [0(2)…10 V,
R
in
> 200 kohm] input selected by switch AI1. Change
of setting requires reboot of control unit.
7)
Current [0(4)…20 mA,
R
in
= 100 ohm] or voltage [0(2)…10 V,
R
in
> 200 kohm] input selected by switch AI2. Change
of setting requires reboot of control unit.
Default I/O diagram of the converter control unit
(UCU-22…24)
The diagram below shows the default I/O connections of the UCU control unit of the
converter, and describes the use of the connections. Under normal circumstances,
the factory-made wiring should not be changed.
The wire size accepted by all screw terminals (for both stranded and solid wire) is
0.5 2.5 mm
2
(22…12 AWG). The tightening torque is 0.45 N·m (4 lbf·in).
DescriptionTerminal
Drive-to-drive linkXD2D
Not in use by default
D2D_B1
1
2
3
4
D2D_A2
BGND3
SHIELD4
Drive-to-drive link termination switch.
1)
XD2D TERM
ON
1
RS485 connectionX485
CIO-01 module connection (optional)
B5
5
6
7
8
A6
BGND7
SHIELD8
X485 bias selection switchX485 BIAS
ON
1
X485 termination switchX485 TERM
ON
1
CAN busXCAN
Not supported
CAN_H9
9
10
11
12
CAN_L10
CAN_CGND11
Control cable shieldCAN_SHLD12
The control unit 71