Pressure
loss
Coolant flow rateCoolant volume
Frame
ACS880-
1607LC-…
kPa
TotalFilter(s)
Power
mod-
ule(s)
TotalCabinetFilter
Power
mod-
ule(s)
l/minl/minl/minllll
120304266.44.41.60.42×R7i0599A-7
120304266.44.41.60.42×R7i0799A-7
Pressure
loss
Coolant flow rateCoolant volume
Frame
ACS880-
1607LC-…
kPa
TotalFilter(s)
Power
mod-
ule(s)
Total
Filter
cabinet
Power
module
cabinet
Power
mod-
ule(s)
l/minl/minl/minllll
U
n
= 690 V
1203620167.12.62.61.9R8i0400A-7
1203620167.12.62.61.9R8i0500A-7
1203620167.12.62.61.9R8i0600A-7
1203620167.12.62.61.9R8i0700A-7
1203620167.12.62.61.9R8i0800A-7
1203620167.12.62.61.9R8i0900A-7
12072403214.25.25.23.82×R8i1000A-7
12072403214.25.25.23.82×R8i1200A-7
12072403214.25.25.23.82×R8i1400A-7
12072403214.25.25.23.82×R8i1600A-7
12072403214.25.25.23.82×R8i1800A-7
Tightening torques
Unless a tightening torque is specified in the text, the following torques can be used.
Electrical connections
Strength classTorqueSize
4.6...8.80.5 N·m (4.4 lbf·in)M3
4.6...8.81 N·m (9 lbf·in)M4
8.84 N·m (35 lbf·in)M5
8.89 N·m (6.6 lbf·ft)M6
8.822 N·m (16 lbf·ft)M8
8.842 N·m (31 lbf·ft)M10
8.870 N·m (52 lbf·ft)M12
8.8120 N·m (90 lbf·ft)M16
Technical data 131

Table of Contents