ABB ACS880-1607LC - Free Space Requirements; Losses, Cooling Data and Noise

ABB ACS880-1607LC
148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WeightDepthWidth
Height
1)
Frame
ACS880-
1607LC-…
kgmmmmmm
1425644160020102×R8i1400A-7
1425644160020102×R8i1600A-7
1425644160020102×R8i1800A-7
1)
The top power cable entry (option +H351) increases height (+50 mm) and width (+300 mm)
Free space requirements
Free space requirements
The values are as required by cooling, maintenance and/or operation of the pressure
relief (if present). Also obey the general mechanical installation instructions.
AboveSidesFront
in.mmin.mmin.mm
9.8525000391000
> 400 mm (15.75 in.)
Losses, cooling data and noise
Effi-
ciency
2)
Noise
Losses
1)
FrameACS880-
1607LC-…
L
PA
4)
L
WA
3)
P
loss
total
P
loss
(filter)
P
loss
(con-
verter)
%dBAdBAkWkWkW
U
n
= 500 V
99.1**1.10.50.6R7i0150A-5
99.1**1.60.61.0R7i0250A-5
99.1**2.10.81.3R7i0350A-5
99.0**2.81.11.7R7i0450A-5
99.0**3.51.52.0R7i0550A-5
99.1**4.11.62.52×R7i0700A-5
99.0**5.42.23.22×R7i0900A-5
99.0**6.72.93.82×R7i1100A-5
U
n
= 690 V
98.9**1.80.71.2R7i0150A-7
98.9**2.30.81.5R7i0200A-7
98.9**3.01.02.0R7i0300A-7
Technical data 129