WeightDepthWidth
Height
1)
Frame
ACS880-
1607LC-…
kgmmmmmm
1425644160020102×R8i1400A-7
1425644160020102×R8i1600A-7
1425644160020102×R8i1800A-7
1)
The top power cable entry (option +H351) increases height (+50 mm) and width (+300 mm)
Free space requirements
■
Free space requirements
The values are as required by cooling, maintenance and/or operation of the pressure
relief (if present). Also obey the general mechanical installation instructions.
AboveSidesFront
in.mmin.mmin.mm
9.8525000391000
Losses, cooling data and noise
Effi-
ciency
2)
Noise
Losses
1)
FrameACS880-
1607LC-…
L
PA
4)
L
WA
3)
P
loss
total
P
loss
(filter)
P
loss
(con-
verter)
%dBAdBAkWkWkW
U
n
= 500 V
99.1**1.10.50.6R7i0150A-5
99.1**1.60.61.0R7i0250A-5
99.1**2.10.81.3R7i0350A-5
99.0**2.81.11.7R7i0450A-5
99.0**3.51.52.0R7i0550A-5
99.1**4.11.62.52×R7i0700A-5
99.0**5.42.23.22×R7i0900A-5
99.0**6.72.93.82×R7i1100A-5
U
n
= 690 V
98.9**1.80.71.2R7i0150A-7
98.9**2.30.81.5R7i0200A-7
98.9**3.01.02.0R7i0300A-7
Technical data 129